Honeywell EK280 Operating Instructions Manual page 53

Volume conversion device
Hide thumbs Also See for EK280:
Table of Contents

Advertisement

Assembly, Connection and Putting into Operation
5.3.1.7
Deleting change information for comparison of Vm with the
gas meter
In order to allow the volume at measurement conditions to be reset if the
administrator lock is open, the change information for comparison of "Vm"
with the gas meter must be deleted:
Open the calibration lock
Move the cursor to the „Serv." tab and go to the value „Clear"
(deleting change information) via the following path:
Serv.
Press the ENTER key  „0" flashes.
Change the value using the arrow keys  or  to „1"
Once you have changed the value, press the ENTER key in order to
confirm your entry. The entry can be cancelled by pressing the ESC
key.  „TimeX" (time stamp of comparison), „Vm_o" (Vm old value),
„Vm_n" (Vm new value) are set to default value.
5.3.1.8
Setting the volume at base conditions
For the EK280 volume conversion device, there is the option available
when commissioning the device to set the volume at base conditions meter
once if the administrator lock is open. It is always possible to set the
volume if the calibration lock is open:
Open the administrator lock or the calibration lock
Move the cursor to the „Serv." tab and go to the value „VbA"
(adjustable volume at base conditions meter) via the following path:
Serv.
Press the ENTER key  One of the value digits flashes.
Move the cursor using the arrow keys  or  to the digits and
change these using the arrow keys  or .
Once you have changed all of the digits, press the ENTER key in
order to confirm your entry. The entry can be cancelled by pressing
the ESC key.
In order to accept the set value, move the cursor to the value „Store"
Press the ENTER key.  „0" flashes.
Change the value using the arrow keys  or  to „1"
Once you have changed the value, press the ENTER key in order to
confirm your entry. The entry can be cancelled by pressing the ESC
key.  „Vb" is assumed for „VbA".
Volume
Actual volume
Volume
Standard volume
Synchronization Vm
Synchronization Vb
53
Clear
VbA

Advertisement

Table of Contents
loading

Table of Contents