Honeywell DR4300 Product Manual page 98

Circular chart recorder
Hide thumbs Also See for DR4300:
Table of Contents

Advertisement

DR4300 Circular Chart Recorder
Lower Display
Prompt
IN TYP
B
EH
EL
JH
JL
KH
KL
NNM
NIC
R
S
TH
TL
W
100 H*[factory setting]
100 L*
100 T**
4-20***
0-20***
* IEC Alpha =
10m***
0.00385
100m***
**IEC Alpha =
200m***
0.00391
0-1***
***These input
0-2***
selections are not
1-5***
available on Limit
0-5***
Control units.
0-10***
2-10***
XMITTR
Lin [factory setting]
Srt
86
Upper Display
Range of Setting
or Selection
INPUT ACTUATION TYPE—This selection specifies what
actuation you are going to use for the input. Be sure that the values
configured for the high and low chart range, alarm setpoint, etc. are
within the measuring range for the selected actuation type.
B thermocouple
E thermocouple high
E thermocouple low
J thermocouple high
J thermocouple low
K thermocouple high
K thermocouple low
NiNiMo thermocouple
Nicrosil-Nisil
R thermocouple
S thermocouple
T thermocouple high
T thermocouple low
W thermocouple
100 Ohm–RTD (high)
100 Ohm-RTD (low)
100 Ohm-RTD (special) –238 to 482°F
4 to 20 Milliamps
0 to 20 Milliamps
0 to 10 Millivolts
0 to 100 Millivolts
0 to 200 Millivolts
0 to 1 Volt
0 to 2 Volts
1 to 5 Volts
0 to 5 Volts
0 to 10 Volts
2 to 10 Volts
Transmitter Input Type—Use this parameter to specify whether
the input should be used as the PV without characterization (linear)
or the square root of the input should be used as the PV.
Linear—No characterization applied to input.
Square Root—PV is the square root of input. For example:
suppose the linear input range is 0 to 5000 and the input type is 0
to 5 volts. Then if input = 2.5 V = 50 %,
DR4300 Circular Chart Recorder Product Manual
Parameter
Definition
105 to 3300°F
–454 to 1832°F
–200 to 1100°F
0 to 1600°F
20 to 770°F
–320 to 2500°F
–20 to 1000°F
32 to 2500°F
thermocouple
0 to 2372°F
0 to 3100°F
0 to 3100°F
–420 to 700°F
–200 to 600°F
0 to 4200°F
–300 to 900°F
–130 to 392°F
=
.50 .7071 70.71%
.7071 x 5000 = 3535 = PV
41 to 1815°C
–270 to 1000°C
–129 to 593°C
–18 to 871°C
–7 to 410°C
–196 to 1371°C
–29 to 538°C
0 to 1371°C
–18.8 to 1300°C
–18 to 1704°C
–18 to 1704°C
–251 to 371°C
–129 to 316°C
–18 to 2316°C
–184 to 482°C
–90 to 200°C
–150 to 250°C
=
4/00