4.3.15 Alarms Set Up Group

Introduction
If the recorder hardware supports outputs, one or both relays can be used for alarming. An alarm is an
indication that an event that you have selected during configuration (process variable, for example) has
exceeded one or more alarm limits. There are two alarms available for each pen (assuming no relay is being
used for control). Each alarm has two setpoints. There are two alarm output selections, high and low. You
can configure each setpoint to alarm either high or low. Each alarm has an adjustable hysteresis of 0.0 % to
100.0 % that is configurable for that alarm's setpoint.
If the "OUTALG" function in the control group is set to "RLYD", both relays on the printed circuit
assembly for the pen being configured are used for control, and the prompts in the alarm group will not be
displayed. If "OUTALG" is "RLY", or if the recorder is a limit controller, then Relay 1 is used for control.
In these cases only the prompts for the second alarm (Relay 2) will be displayed.
If "TIMER" is set to "ENAB", then Relay 2 is used by the timer and prompts for the second alarm will not
be displayed.
Alarms group prompts
Table 4-13 lists all the function prompts in the alarms set up group and their definitions.
For a 2-pen recorder, the desired input channel is displayed on the left side of the operator interface.
Press FUNC to select channel.
Press SETUP key until "ALARMS" appears in the lower display.
Press FUNC key to select the parameters.
Lower Display
Prompt
A1S1TY*
A1S2TY*
*For Deviation Alarm to function: control must be enabled. If On/Off control is selected, only alarm #2 is available for Deviation.
A1S1VA
A1S2VA
106

Table 4-13 Alarm Parameter Definitions

Upper Display
Range of Setting
or Selection
NONE [factory setting]
INP
DEV
Same as A1S1TY
–999 to 9999
[factory setting = 100]
–999 to 9999
[factory setting = 100]
DR4300 Circular Chart Recorder Product Manual
Parameter
Definition
ALARM 1 SETPOINT 1 TYPE—Select what you want
Setpoint 1 of Alarm 1 to represent.
NO ALARM
INPUT PV
DEVIATION of input from setpoint
ALARM 1 SETPOINT 2 TYPE—Select what you want
Setpoint 2 of Alarm 1 to represent. The selections are the
same as A1S1TY.
ALARM 1 SETPOINT 1 VALUE—This is the value at
which you want the alarm type chosen in prompt
"A1S1TY" to actuate. The appropriate value depends on
what the setpoint has been configured to represent.
ALARM 1 SETPOINT 2 VALUE—This is the value at
which you want the alarm type chosen in prompt
"A1S2TY" to actuate. The appropriate value depends on
what the setpoint has been configured to represent.