DR4300 Circular Chart Recorder
C.4 Setpoint Program Prompt Hierarchy
Table C-1 lists all the function prompts for Setpoint Program data configuration in the order of their
appearance. These prompts are available when SPPROG is enabled in the SPRAMP set up group described
in Section 4.
All parameters may be changed while the program is disabled or in HOLD.
Lower Display
Prompt
SPPROG
START 1
END 1
START 2
END 2
START 3
END 3
START 4
END 4
RECYCL
SOKDEV
220
Table C-1 Prompt Hierarchy and Available Selections
Upper Display
Range of Setting
or Selection
DIS
ENAB
1,3,5,7,9,11,13,15,17,19,
21,23 [factory setting=1]
2,4,6,8,10,12,14,16,18,20,22
,24 [factory setting=6]
1,3,5,7,9,11,13,15,17,19,
21,23 [factory setting=7]
2,4,6,8,10,12,14,16,18,20,22
,24 [factory setting=12]
1,3,5,7,9,11,13,15,17,19,
21,23 [factory setting=13]
2,4,6,8,10,12,14,16,18,20,22
,24 [factory setting=18]
1,3,5,7,9,11,13,15,17,19,
21,23 [factory setting=19]
2,4,6,8,10,12,14,16,18,20,22
,24 [factory setting=24]
0 to 99
[factory setting=0]
–99.9 to 99.9 engineering
units
[factory setting=0.00]
DR4300 Circular Chart Recorder Product Manual
Parameter
Definition
SETPOINT PROGRAMMING—This must be set to ENAB
for the setpoint program feature to work, and for the
associated operating parameters to be displayed.
SPRAMP must be disabled. (See Section 4.)
DIS—Disabled
ENAB—Enabled
START SEGMENT FOR PROGRAM 1—Enter the
number of the first segment in Program 1.
END SEGMENT FOR PROGRAM 1—Enter the number
of the last segment in Program 1.
START SEGMENT FOR PROGRAM 2—Enter the
number of the first segment in Program 2.
END SEGMENT FOR PROGRAM 2—Enter the number
of the last segment in Program 2.
START SEGMENT FOR PROGRAM 3—Enter the
number of the first segment in Program 3.
END SEGMENT FOR PROGRAM 3—Enter the number
of the last segment in Program 3.
START SEGMENT FOR PROGRAM 4—Enter the
number of the first segment in Program 4.
END SEGMENT FOR PROGRAM 4—Enter the number
of the last segment in Program 4.
RECYCLES—Enter the number of times the program
selected for execution will be repeated.
SOAK DEVIATION—Enter the acceptable deviation from
setpoint during a soak cycle. If the PV differs from the
setpoint by more than the value of SOKDEV, soak time is
frozen.
There are no guaranteed soaks if SOKDEV = 0.
4/00