Condition
Input Filter
Case
Pen
Chart
Wiring Connections
Color
Weight
Mounting
Installation Category
(Overvoltage Category)
Pollution Degree
EMC Classification
Dielectric Insulation
Options
Current Output (Isolated)
Electromechanical Relay
Output
3/00
Without Display: Analog with time constant of 3 seconds and digital with time
constant of 1 second.
With Display: Analog with time constant of 3 seconds and digital adjustable 0
seconds to 120 seconds.
Molded, foamed-Noryl with gasketed door to meet NEMA 3 enclosure
requirements.
Disposable fiber-tip ink cartridge, line length per cartridge more than 305 m
[1000 ft]
One Pen: Purple
Two Pen: Purple (pen 1) and red (pen 2)
NOTE: Only pen 1 (purple) is referenced to the chart time line.
262 mm [10.32-inch] diameter chart with standard preprinted markings and a
calibrated width of 100 mm [4 inches].
Screw terminals (2 piece)
Case: Black
Door: Standard—Gray; Optional—Carribean blue or black
5.4 kg [12 lbs]
Panel-, pipe- or surface-mounted
Category II: Energy-consuming Equipment Supplied from the Fixed Installation,
Local Level Appliances, and Industrial Control Equipment (EN61010-1).
Pollution Degree 2: Normally Non-conductive Pollution with Occasional
Conductivity Caused by Condensation (Ref. IEC 664-1).
Group 1, Class A: ISM Equipment (EN55011, emissions), Industrial Equipment
(EN50082-2, Immunity).
AC Main to Inputs/Outputs
Input to Input
Input to Output
(except Digital Input to Current Output)
AC Main to Transmitter Power
Range can be set anywhere between 4 mA and 21 mA, and as direct or reverse
action.
Resolution: 11 bits for 4 mA to 21 mA
Accuracy: 0.5 % full scale
Temperature Stability: 0.1 % F.S./°C
Load Resistance: 0 ohms to 600 ohms
SPDT contacts. Internally socketed.
Resistive Load: 5 A @ 120 Vac or 2.5 A @ 240 Vac or 30 Vdc.
Inductive Load: 50 VA @ 120 Vac or 240 Vac.
Motor: 1/6 H.P.
DR4300 Circular Chart Recorder Product Manual
Specifications
250 Vac
250 Vac
250 Vac
250 Vac
Installation