5.5 Input Calibration Procedure
Introduction
Before performing this procedure, be sure the recorder is wired for calibration as described in Subsection
5.4. Apply power and allow the recorder to warm up for 30 minutes before you calibrate.
Make sure "LOCK" is set to "NONE" (see Section 4 - Configuration, Startup and Operation of Recorder
with Display).
ATTENTION
For Milliamp inputs, be sure the current source is at zero before switching on the calibrator.
Do not switch the calibrator on/off while it is connected to the recorder's input. Failure to observe
this precaution could result in damage to input circuits.
Calibration procedure sequence
The calibration procedure sequence for all inputs is listed in Table 5-9. The calibration procedure for inputs
1 and 2 is identical. The displays indicate the input number.
Press the
FUNC
Step
Description
1
Enter Calibration Mode
4/00
key to change display as required (INP1 or INP2).
Table 5-9 Input Calibration Procedure Sequence
Press
SET
UP
until you see
FUNC
DR4300 Circular Chart Recorder Product Manual
Input and Output Calibration for Recorder with Display
Action/Result
Upper Display
CAL
Lower Display
INPUT
If "CAL" doesn't appear or prompt access is declined,
check "LOCK" configuration.
You will see:
Upper Display
DIS
Lower Display
CAL IN
The calibration sequence is enabled and you will see:
Upper Display
BEGIN
Lower Display
CAL IN
151