DR4300 Circular Chart Recorder
+ White
J
•
- Red
+ Yellow
K
- Red
+ Blue
T
- Red
+ Black
R
- Red
+ Black
S
- Red
+ Purple
E
- Red
+ Gray
B
- Red
+ Orange
N
- Red
Standard used as color
reference ANSI MC96.1
32
Main PCA
Pen 2
7
TB1
Thermocouple
+
T/C
RTD
+
RTD
mA, mV or Volt
+
mA, mV or
Volt source
Figure 2-11 Analog Input Wiring
DR4300 Circular Chart Recorder Product Manual
7
TB2
TB1
TB2
Be sure that thermocouple
–
extension wire matches
thermocouple type
R
• 100 ohm maximum lead resistance
• Keep resistance of all wires equal
TB2
•
Use 18 gauge copper wire for lengths up
to 150 feet.
•
For two wire RTD jumper terminal
–
negative (-) to R.
R
• Many 3-wire RTDs use color coded
wires. One wire is a different color than
the other two. The single wire is usually
the positive connection
TB2
–
R
Main PCA
Pen 1
TB2
24086