Pneumatic Module; Pneumatic Module With Single Acting Relay - GE Masoneilan SVI II ESD Installation And Maintenance Manual

Smart valve interface with sil3 emergency shutdown pst controller
Table of Contents

Advertisement

Position Transmitter (AO)
The SVI II ESD has the ability to retransmit the position signal as an output to another device
with 4 - 20 mA current output proportional to position. Enter a lower range value and an upper
range value.

Pneumatic Module

The pneumatic module consists of an I/P and relay assembly.
Current-to-Pressure Converter, I/P
The I/P converts a current signal into a pressure signal in the following manner. A fixed coil
creates a magnetic field proportional to the applied current. The field magnetically pulls a
flexure towards a nozzle to increase pressure on the flexure. The pressure on the flexure
increases in response to a coil current increase. Coil encapsulation of the provides protection
from environmental pollution.
Single Acting Pneumatic Relay
The single acting pneumatic relay amplifies the pressure from the I/P and increases airflow as
required for stable, responsive, actuator performance. Single acting relay operates on any
supply pressure that is at least 5 psi (.345 bar, 34.5 kPa) above the required actuator pressure,
up to 100 psi (6.9 bar, 690 kPa).
130 |
=GE Oil & Gas
Figure 76 Pneumatic Module with Single Acting Relay
I/P Current to Pneumatic Converter
Relay
(Pneumatic Amplifier)
Vent
© 2016 General Electric Company. All rights reserved.