GE Masoneilan SVI II ESD Installation And Maintenance Manual page 146

Smart valve interface with sil3 emergency shutdown pst controller
Table of Contents

Advertisement

Sequence
Byte
Bit
#
#
5
6
SELF_
CHECK
47
5
7
SOFTWARE
48
6
0
ESD_TRIP
(_ACTIVE)
49
6
1
ESD_NEW_
DATA
50
6
2
ESD_DATA_
ERROR
51
146 |
=GE Oil & Gas
Table 12 SVI II ESD Fault Matrix (Continued)
FAULT Name
Criticality
of Alarm
1
2
1
3
3
Auto-
Can be
Non-
mati-
cleared/
Mas-
cally
Persists
kable/
cleared
across
Annunci-
resets
ated
No
Yes/No
Yes/No
No
Yes/No
Yes/Yes
Yes
No/No
No/No
No
No/Yes
No/No
Yes
Yes/No
No/No
TEXT For
Probable Cause
DD &
English
ValVue
ESD2
English
Self
1-A general self
Check
check failed.
Error
Soft-
Operating system
ware
failed in conduct-
Error
ing a task.
ESD
SVI II ESD suc-
Valve
cessfully de-ener-
Tripped
gized its
pneumatic out-
put.
New ESD
A shutdown event
Data
is stored in mem-
available
ory and has not
yet been archived
by ValVue ESD.
Saving
Upon a safety trip
ESD data
(shutdown), a
error
problem occurred
when storing
event in memory.
© 2016 General Electric Company. All rights reserved.
Recommended
Action
1- Clear the condi-
tion using ValVue
®
ESD or HART
Host.
2- If condition per-
sists, replace
device and report
problem at svi-
support@GE.com.
1- Clear the condi-
tion using ValVue
®
ESD or HART
Host.
2- If condition per-
sists, replace
device and report
problem at svi-
support@GE.com.
None. This is a
status to confirm
that SVI II ESD
successfully
de-energized its
output.
Connect ValVue
ESD and wait for
flag to self-clear.
This will indicate
that ValVue ESD
successfully
archived signa-
ture in its data-
base.
1- Clear the condi-
tion using ValVue
®
ESD or HART
Host.
2- If condition per-
sists, replace
device and report
problem at svi-
support@GE.com.

Advertisement

Table of Contents
loading