Svi Ii Esd Maintenance; Repair And Replacement; Factory Notification - GE Masoneilan SVI II ESD Installation And Maintenance Manual

Smart valve interface with sil3 emergency shutdown pst controller
Table of Contents

Advertisement

SVI II ESD Maintenance

Repair and Replacement

Repairs may be made only by the factory authorized personnel trained to repair Safety
Devices.
1. A conservative approach is taken in estimating the service interval for the digital valve
controller in Safety Instrumented Systems. For SIS applications, perform preventive
maintenance on the SVI II ESD after five years from the shipment date, if the average daily
ambient temperature is below 60°C (140°F). Where ambient temperature exceeds 60°C
(140°F) for extended periods, reduce this maintenance interval based on plant experience.
2. SVI II ESD preventive maintenance consists of replacing gaskets, O-rings in the device and
a visual inspection of moving components to verify satisfactory condition. Following
maintenance, the SVI II ESD must be reinstalled on the valve actuator and calibrated per
the procedures. After calibration, validate the SVI II ESD functional safety. All maintenance
procedures must be performed only by the factory authorized personnel trained to repair
Safety Devices.
3. If alarms or alerts are detected during operation, maintenance or periodic inspection and
test, immediately take corrective action according to the troubleshooting and repair
procedures given in the Instruction Manual.
4. The tools required for repair of the SVI II ESD are also listed in the SVI II ESD Instruction
Manual, EW5000-ESD.

Factory Notification

Report any failures detected that compromise functional safety to the factory. Contact your
local the factory service representative. Sales Office locations are listed on the back cover of
this document.
84 |
=GE Oil & Gas
When working on safety rated equipment appropriate risk
CAUTION
reduction safety measures must be in place.
GE does not assume responsibility for the selection, use, or
NOTE
maintenance of any product. Responsibility for proper selection,
use of any GE product remains solely with the purchaser and
end-user. The SVI II ESD requires recertification, which must be
performed by factory authorized personnel trained to repair
Safety Devices.
© 2016 General Electric Company. All rights reserved.