Mounting Bracket
Magnet Holder
Pole Ring
Levers
®
HART
Physical Device Type
DD Registered with HART
Communication Foundation
ValVue ESD Application
Yokogawa PRM
DD for Handheld
®
HART
CMD #3
Air Supply
Action
Supply Pressure
Air Delivery - Single Acting
Relay
Air Capacity (flow coefficient)
158 |
=GE Oil & Gas
Table 17 Construction Material Specifications
300 series stainless steel
Corrosion Protected Anodized Aluminum 6061 T6
416 stainless steel
300 Series stainless steel
Table 18 System Connectivity
®
Actuator; HART
®
Yes, available through HART
ValVue ESD Plug-In application available
Yes
®
HART
4-20 mA input signal
PV = Valve Position, 0-100%
SV = Actuator Pressure (P1-P2)
TV = Supply Pressure
QV = P2 for double acting units (not applicable)
Table 19 Pneumatics Single Acting Standard Flow
Dry, oil-free, 5 micron filtered air (See ISA S7.3)
Direct
30-120 psi max. (2.07 - 8.27 bar, 207 - 827 kPa)
Regulated 10 psi above actuator spring range. Do not exceed actuator rating.
11.48 scf/min. (325 sL/min.) filling, 14.12 scf/min. (400 sL/min.) venting at 30 psi
(2.1 bar, 207 kPa) supply
19.25 scf/min. (545 sL/min.) filling, 23.48 scf/min. (665 sL/min.) venting at 60 psi
(4.14 bar, 414 kPa) supply
27 scf/min. (765 sL/min.) filling, 32.84 scf/min. (930 sL/min.) venting at 90 psi
(6.21 bar, 621 kPa) supply
34.6 scf/min. (980 sL/min.) filling, 42.37 scf/min. (1200 sL/min.) venting at 120 psi
(8.28 bar, 828 kPa) supply
Loading
CV = 0.57
Venting
CV = 0.53