Quick Start

Installation and initial startup procedures for the CPUE05 include the following steps. Before installing and operating the
CPUE05, refer to VersaMax PLC User's Manual, GFK-1503 for detailed information.

Pre-Installation check

Carefully inspect all shipping containers for damage. If any equipment is damaged, notify the delivery service
immediately. Save the damaged shipping container for inspection by the delivery service. After unpacking the
equipment, record all serial numbers. Save the shipping containers and packing material in case it is necessary to
transport or ship any part of the system.

Module Installation

This equipment may be mounted on a horizontal or vertical DIN rail. If mounted on a vertical DIN rail, the CPU module
must be located at the bottom. The CPU and connecting carriers must be installed on the same section of 35mm (1.38in)
x 7.5mm (.3in) DIN rail, 1mm (.04in) thick. Steel DIN rail is recommended. The DIN rail must be electrically grounded to
provide EMC protection. The rail must have a conductive (unpainted) corrosion-resistant finish. DIN rails compliant with
DIN EN50022 are preferred. For vibration resistance, the DIN rail should be installed on a panel using screws spaced
approximately 15.24cm (6in) apart.
Rated thermal specifications for the CPU module are based on a clearance of 50.8mm (2in) above and below the
equipment and 25.4 mm (1 inch) to the left of the CPU module.
1.
Allow sufficient finger clearance for opening CPU door.
2.
Allow adequate clearance for serial port and Ethernet cables.
3.
Allow adequate space for power wiring.
The CPU with power supply attached fits into a 70mm (2.76in) deep enclosure.
Installing the CPU on the DIN Rail
The CPU snaps easily onto the DIN rail. No tools are required for mounting or grounding to the DIN rail.
Before joining module carriers to the CPU, remove the connector cover on the right-hand side of the CPU. Do not
discard this cover: you will need to install it on the last carrier, to protect the connector pins from contamination and
damage during use.
CPU with Embedded Ethernet Interface
IC200CPUE05