Troubleshooting; Overview; Internal Diagnostics - GE Masoneilan SVI II ESD Installation And Maintenance Manual

Smart valve interface with sil3 emergency shutdown pst controller
Table of Contents

Advertisement

9. Troubleshooting

Overview

One of the key features of SVI II ESD is the ability to diagnose and announce any SIS failure. This
section provides information describing the SVI II ESD diagnostics and how to use the diagnostic
information to troubleshoot the cause of the problem.

Internal Diagnostics

SVI II ESD performs internal self-diagnostics and hardware checks. When ValVue ESD or HART
Handheld or the local display indicates that there are error messages write them down for
troubleshooting.
Diagnostic information is a crucial function of SVI II ESD operation. There are several methods
to perform diagnostics and to view diagnostic data. The SVI II ESD has:
Internal Diagnostics that automatically run every hour
Partial Stroke Diagnostics that are user configurable through ValVue ESD
Step, Extended Signature and Terminal Board diagnostics that are available through
ValVue ESD only