Input Signal, Power, And Display Specifications; Construction Material Specifications - GE Masoneilan SVI II ESD Installation And Maintenance Manual

Smart valve interface with sil3 emergency shutdown pst controller
Table of Contents

Advertisement

IEC61508 Up to SIL3 per TUV, Type A Device (Simplex, Low Demand), SIL3 Safety Shutdown Function, Safe Failure Frac-
tion with PVST: 99.1%
Signal
Power Supply
Compliance Voltage Rating
Minimum Current Cutoff
Minimum Terminal Voltage
Current Signal
ESD in Voltage
ESD IN current draw
Wire Size
Strip Length
Digital Communication
Local Display Liquid Crystal (optional)
Push Buttons
Housing and Cover
Weight
Relay and Manifold
I/P Motor
© 2016 General Electric Company. All rights reserved.
Table 15 Operational Specifications (Continued)
Table 16 Input Signal, Power, and Display Specifications
4/20 mA with HART
Taken from 4-20 mA control signal (ASD and A/DSD)
ASD - 9.6 V at 20 mA, 11.0 V at 4.0 mA
DSD - 24 V at 12 mA
A/DSD - 9.6 V at 20 mA, 11.0 V at 4.0 mA
3.2 mA
9.5 VDC @ 20 mA
< 5.6 mA = de-energized output, >15 mA = energized output
0 (trip), 24 VDC energized output
< 9.5 mA
14/28 AWG
0.22 in / 6 mm
®
HART
personal computer or a handheld device. HART
mode.
Three lines of nine alpha numeric characters.
Display becomes unreadable between 0 °C and -10 °C.
Display is shutdown at -15 °C.
Three Explosion Proof / Flameproof push buttons
Table 17 Construction Material Specifications
Aluminum ASTM B85 SC84B standard
Stainless Steel optional (316L) Note: SST version is also SIL3
Standard - 7.4 lbs./ 3.357 kg
Stainless Steel - 16 lbs/ 7.257 kg
Single Acting - PPS, 300 Series Stainless Steel, nitrile diaphragms
430 stainless steel, PPS, 300 series stainless steel
®
Communication Protocol
Communication protocol signal from ValVue ESD software on a
Masoneilan SVI II ESD Installation and Maintenance Manual
®
point-to-point and burst
| 157
=