GE Masoneilan SVI II ESD Installation And Maintenance Manual page 152

Smart valve interface with sil3 emergency shutdown pst controller
Table of Contents

Advertisement

Sequence
Byte
Bit
#
#
9
1
AIR_LATCH_
DISABLED
74
9
2
AIR_LATCH_
DELAY
75
152 |
=GE Oil & Gas
Table 12 SVI II ESD Fault Matrix (Continued)
FAULT Name
Criticality
of Alarm
3
3
Auto-
Can be
Non-
mati-
cleared/
Mas-
cally
Persists
kable/
cleared
across
Annunci-
resets
ated
No
Yes/No
No/Yes
Yes
No/Yes
No/Yes
TEXT For
Probable Cause
DD &
English
ValVue
ESD2
English
Air Latch
Cannot latch due
HW Mal-
to Low Supply
function
Pressure due to
one or more of
the position or
pressure sensors
faults.
Airloss Latching
disabled due to
faulty sensor(s)
No Rec.
Cannot latch
Delay
because Air Latch
Specified
Delay was not set
-- would have
never recovered if
latched.
Airloss Latching
delay is not
entered. Cannot
recover.
© 2016 General Electric Company. All rights reserved.
Recommended
Action
If persists contact
GE.
Implemented for
firmware 3.1.6.
If persists contact
GE.
Implemented for
firmware 3.1.6.