When installing an SVI II ESD for the first time you have to perform configuration before
calibration because configuration can affect calibration.
If a change is made in the Air-to-Open / Air-to-Close configuration option or if you move the
SVI II ESD to a different valve or make any change to the valve position linkage, you must run
the find STOPS calibration again.
CONFIG
*
Air to
Menu
Press * to select option.
Press + or - to accept and
proceed to next menu item.
Air to....Menu
ATO
*
ATC
Select Air To Open (ATO)
or Air To Close (ATC). Must
match the actuator exactly.
© 2016 General Electric Company. All rights reserved.
CONFIGuration Menu
See Figure 62 on
page 102 for full menu
+
Pressure
Units
Pressure Units
*
Select display
units for pressure.
Figure 63 CONFIGure Menu
+
Menu
Menu
PSI
*
BAR
*
KPA
Select display language.
Masoneilan SVI II ESD Installation and Maintenance Manual
CONFIG
*
+
Language
Setup
Menu
Language
Menu
*
ENGLISH
*
FRENCH
+/-
*
SPANISH
*
PORTUGUESE
*
JAPANESE
*
ITALIAN
*
GERMAN
+
| 103
=