Sequence
Byte
Bit
#
#
7
5
SUPPLY_
DROOP
(Supply deviation)
62
7
6
SUPPLY_LOW
63
7
7
SUPPLY_
HIGH
64
8
0
IP_CAL_
DRIFT
65
© 2016 General Electric Company. All rights reserved.
Table 12 SVI II ESD Fault Matrix (Continued)
FAULT Name
Criticality
of Alarm
2
3
3
2
Auto-
Can be
Non-
mati-
cleared/
Mas-
cally
Persists
kable/
cleared
across
Annunci-
resets
ated
Yes
Yes/Yes
No/Yes
Yes
No/Yes
No/No
Yes
No/Yes
No/Yes
No
Yes/No
No/Yes
Masoneilan SVI II ESD Installation and Maintenance Manual
TEXT For
Probable Cause
DD &
English
ValVue
ESD2
English
Air Sup-
1- The air supply
ply
droop measured
Droop
during a PST is
Abnor-
above the config-
mal
ured threshold.
2- The filter in air
filter/regulator is
clogged up.
3- Air supply tub-
ing is too small.
4- Insufficient vol-
ume of air supply
manifold.
Low Air
1- An air supply
Supply
loss occurred.
Warning
2- Nearby equip-
ment draws a
high volume of air.
3- The air set is
adjusted less than
the configured
threshold.
High Air
1-A failure in the
Supply
air filter regulator
Warning
occurred.
2- A nearby
equipment draw-
ing a high volume,
suddenly quit
using air and cre-
ated a spike in air
supply.
3- The air set is
adjusted greater
than configured
threshold.
I/P Cali-
1- The current to
bration
pressure con-
Drift
verter's flexure
Warning
has been tam-
pered with or mis-
adjusted.
2- An impending
failure is present
in the flow regula-
tor of the I/P.
Recommended
Action
1- Verify proper
setting of thresh-
old.
2- Replace filter in
the air set.
3- Increase tub-
ing size between
air set and SVI II
ESD.
4- Re-size mani-
fold.
1- Confirm that
operations may
be returned to
normal, then turn
on air supply.
2- Resize air mani-
fold.
3- Increase air
pressure to 10psig
more than upper
spring range and
more than 30psig.
1- Replace air fil-
ter regulator.
2- Resize air mani-
fold.
3-Adjust thresh-
old to be 3-5 psig
greater than set
air supply.
1,2 - Service
required. Contact
the factory.
| 149
=