Intrinsic Safety
Flameproof
Energy Limited
Approval Standards
Explosion Proof
Dust Ignition Proof
Certified CL II; Div. 2; GR F, G
Certified CL III; Div. 2
Certified CL I; Div. 2; GR, B, C, D
Intrinsically Safe
Approval Standard
Explosion Proof
Dust Ignition Proof
Suitable for CL II, III; Div. 2; GR F, G
Non-incendive
Intrinsically Safe
Approval Standards
162 |
=GE Oil & Gas
Table 26 ATEX Approvals
Gas: II 1G EEx ia IIC T6 / T5 / T4
Dust: II 1D T96°C
Gas: II 2G EEx dm IIB + H2 T6 / T5 / T4
Dust: II 2D T96 °C
Gas: II 3G EEx nL IIC T6 / T5
Dust: II 3D T96 °C
EN50014: 1997, EN50281-1-1, EN60079-26, EN50020,
EN60069-15, EN1127-1, EN50018, EN50028
Table 27 CSA International Certifications
Table 28 FM Approvals
Table 29 Temperature Class
T6 = 60°C (160°F), T5 = 75 °C (167°F), T4 = 85°C (185°F)
CL I; Div. 1; GR B, C, D T6 / T5 / T4
CL II/III; Div. 1; GR E, F, G T6 / T5 / T4
CL I, II, III; Div. 1; GR A, B, C, D, E, F, G T6 / T5 /
T4
CAN/CSA-C22.2 # 94-M91,142-M198,
157-92, 213-M198, 60529:05
CL I; Div. 1; GR B, C, D T6 / T5 / T4
CL II/III; Div. 1; GR E, F, G T6 / T5 / T4
CL I; Div. 2; GR A, B, C, D
CL I, II, III; Div. 1; GR A, B, C, D, E, F, G
Class 3600, 3615, 3810, ANSI/NEMA 250, IEC
60079-18 IEC60529 +A1
© 2016 General Electric Company. All rights reserved.