GE Masoneilan SVI II ESD Installation And Maintenance Manual page 143

Smart valve interface with sil3 emergency shutdown pst controller
Table of Contents

Advertisement

Sequence
Byte
Bit
#
#
2
1
IP_OUT_OF_
RANGE
18
2
2
TEMPR_
OUT_OF_
19
RANGE
2
3
FACTORYWRITE
20
2
4
Undefined
21
(reserved)
2
5
Undefined
22
(reserved)
2
6
Undefined
23
(reserved)
2
7
Undefined
24
(reserved)
3
0
NVM_
CHECKSUM
25
3
1
RAM_
CHECKSUM
26
3
2
FW_
CHECKSUM
27
3
3
STACK
28
3
4
FACTORYMODE
29
© 2016 General Electric Company. All rights reserved.
Table 12 SVI II ESD Fault Matrix (Continued)
FAULT Name
Criticality
of Alarm
1
2
3
3
3
3
3
1
2
1
2
1
Auto-
Can be
Non-
mati-
cleared/
Mas-
cally
Persists
kable/
cleared
across
Annunci-
resets
ated
No
Yes/No
Yes/No
Yes
Yes/No
No/Yes
NA
NA/NA
No/Yes
NA
NA/NA
No/No
NA
NA/NA
No/No
NA
NA/NA
No/No
NA
NA/NA
No/No
No
No/No
Yes/Yes
No
Yes/No
Yes/Yes
No
No/No
Yes/Yes
No
Yes/No
Yes/Yes
No
Yes/No
Yes/No
Masoneilan SVI II ESD Installation and Maintenance Manual
TEXT For
Probable Cause
DD &
English
ValVue
ESD2
English
I/P Out
1- The loop cur-
Of Range
rent to the inter-
nal
current-to-pres-
sure converter is
outside of normal
range.
Temp.
The board tem-
Out Of
perature is below
Range
-40 °C or above
85 °C.
Reserved
NA
(2-3)
Reserved
NA
(2-4)
Reserved
NA
(2-5)
Reserved
NA
(2-6)
Reserved
NA
(2-7)
NVM
1- A permanent
Check-
corruption of the
sum
content in
Error
non-volatile
memory
occurred.
RAM
1- A corruption of
Check-
the content in vol-
sum
atile memory
Error
occurred.
Flash
1- Invalid firm-
Check-
ware checksum
sum
due to data cor-
Error
ruption.
Stack
1- A problem with
Error
the memory stack
occurred.
Factory
1- Device is in the
Mode
factory mode.
Fault
Recommended
Action
NOT IMPLE-
MENTED
NOT IMPLE-
MENTED
NOT IMPLE-
MENTED
NOT IMPLE-
MENTED
NOT IMPLE-
MENTED
NOT IMPLE-
MENTED
1- Remove power
to the device for 2
minutes and
restart the device.
2- If the failure
persist, replace
the device.
1- Notify factory
at svisup-
port@GE.com.
1- Remove power
to the device for 2
minutes and
restart it.
2- If the failure
persists, Replace
device.
1- Clear the condi-
tion using ValVue
®
ESD or HART
Host.
1- Replace device
and report the
problem at svi-
support@GE.com.
| 143
=