Ex ample trace: SLS (without encoder) with STOP A
①
Drive_1.r9714[0]: SI motion diagnostics velocity, load-side velocity actual value at the Control Unit
②
Active SLS level bit 1
③
Active SLS level bit 0
④
SLS active
⑤
Internal event
⑥
STO active
⑦
STOP A or B active
⑧
Select SLS bit 1
⑨
Select SLS bit 0
⑩
Deselect SLS
Image A-18
Example trace: SLS (without encoder) with STOP A
Trace evaluation:
● SLS function with SLS level 1 is active (see bits "deselection SLS", "selection SLS bit 0",
"selection SLS bit 1" and "SLS active", "active SLS level bit 0" and "active SLS level
bit 1")
● Drive is accelerated beyond the SLS limit (time axis from approx. -800 ms)
● Exceeding the limit is recognized (time axis 0 ms)
● Safety fault is initiated (time axis 0 ms; bit "internal event" is set to 0)
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
A.3 Acceptance tests (recommendations)
Appendix