1. In HW Config, create a PROFINET-capable F-CPU, e.g. CPU 317F-2 PN/DP,
corresponding to the hardware that has been installed. Create a PROFINE T subnet and
configure the F-CPU as an IO controller. Information about configuring an IO controller of
the F-CPU 317F-2 can be found here:
References: SIMATIC PROFINET IO Getting Started: Collection
2. In the standard module catalog under PROFINET IO, choose the module that you want to
connect to the PROFINET IO subnet as an IO device, e.g. a CU320-2.
3. Drag the module onto the line of the PROFINET IO subnet. The IO device is inserted.
The "Properties > Ethernet Interface SINAMICS-S120" window opens. An IP address is
already recommended there and the subnet selected. Confirm with "OK" to accept the
setting.
4. Save and compile the settings in HW Config, and then load them to the target device.
This sets up a PROFIsafe connection between the F-CPU and the SINAMICS S120