Not e
Non-c ritical alarms
When evaluating the alarm buffer you can tolerate the following alarms:
• A01697 SI Motion: Motion monitoring test required
• A35014 TM54F: Test stop required
These alarms occur after every system startup and can be evaluated as non-critical.
• A01699 SI CU: Shutdown path test required
This alarm occurs after the time in p9659 has expired.
You do not need to include these alarms in the acceptance report.
Not e
No ac c eptance test with alarm A01796
If the alarm A01796 is active, the pulses are safely canceled, and an acceptance test is not
possible.
Acceptance test support in STARTER
The STARTER commissioning tool offers you the option of creating the acceptance report
semi-automatically:
1. In STARTER, select <Drive device> → Documentation and double-click on Acceptance
documentation.
2. Select the name for the file and the template to be used.
3. To generate the acceptance report, click on Creat e.
A Word document with the following contents is generated:
– Firmware versions (actual parameter values have already been entered)
– Monitoring cycles
– Checksums
– Parameter assignment of the Safety functions
For the above points, the actual parameter values have already been entered.
– Tables to perform the acceptance test step-by-step
Acceptance test support using STARTER script
You will find a STARTER script on the following Internet page to help you with acceptance
tests:
http://support.automation.siemens.com/WW/view/de/52248627
A PDF with a detailed description of the script is provided at the same link.
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
You must manually complete these tables while the acceptance test is being
performed.
A.3 Acceptance tests (recommendations)
Appendix
421