Siemens Sinamics S120 Function Manual page 441

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

N o .
C01714 (x00), C30714 (x00); x = 1...4 depending on the SLS level (safely limited
speed exceeded)
C01701, C30701 (STOP B initiated)
C01700, C30700 (STOP A initiated)
4.
Analyze trace:
If r9714[0] exceeds the active SLS limit, a safety message (r9722.7 = 0) becomes
active
A STOP B is initiated as a consequence (with subsequent stop STOP A)
5.
Save/print the trace and add it to the acceptance report (refer to the example below)
6.
Acknowledge safety messages and, if required, deselect SLS
No safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7]) at the drive and
TM54F (if one is being used).
Acknowledge switch-on inhibit and run the drive
Check whether the drive is moving
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
D e scri p ti o n
A.3 Acceptance tests (recommendations)
Appendix
Sta tu s
441