Acceptance test for Safe Direction with encoder (Extended Functions)
SDI positive/negative with encoder and stop response "STOP A"
N o .
N o te:
The acceptance test must be individually performed for each configured control and for both directions of rotation.
Control can be realized without selection via TM54F, onboard terminals (CU310-2) or via PROFIsafe.
1.
Initial state
Drive in the "Ready" state (p0010 = 0)
Safety Integrated Extended Functions enabled (p9601.2 = 1)
Safety functions enabled (p9501.0 = 1)
Safety configured with encoder (p9506 = 0 or p9506 = 2)
For "Motion monitoring without selection (Page 205)":
- "SDI positive or negative" activated (p9512.12 = 1 or p9512.13 = 1)
SDI enabled (p9501.17 = 1)
SDI positive deselected (r9720.12 = 1) and SDI negative deselected (r9720.13 = 1)
Note: The parameterized SDI monitoring is already active for motion monitoring with-
out selection.
No Safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7]) at the drive and
TM54F (if used); see note "Non-critical alarms" at the beginning of Section "Ac-
ceptance test."
2.
It may be necessary to take measures in the higher-level controller to be able to exceed the SDI tolerance.
Note that the internal limits (r9733[0], r9733[1] and r9733[2]) are removed by selecting "Start acceptance test".
3.
Configure and activate trace recording
Trigger: Trigger on variable - bit pattern (r9722.7 = 0)
Record the following values: r9713[0], r9721, r9722
Select the time interval and pretrigger so you can recognize when the active SDI
tolerance has been exceeded and the subsequent drive responses
For better analysis, display the following bit values:
r9721.12 (STOP A or B active)
r9722.0 (STO active; set for STOP A)
r9722.7 (internal event; set to 0 when the first safety message occurs)
r9722.12 (SDI positive active) or r9722.13 (SDI negative active)
Select SDI positive or SDI negative
Note: The parameterized SDI monitoring is already active for motion monitoring without selection.
Switch-on the drive and traverse in the negative or positive direction of rotation
Check whether the drive is moving, and after the SDI tolerance (p9564) has been
exceeded that it is coasting down or a configured holding brake is closed
Check whether the following safety messages are pending:
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
D e scri p ti o n
A.3 Acceptance tests (recommendations)
Appendix
Sta tu s
455