Siemens Sinamics S120 Function Manual page 275

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Safe s top functions (SS1, SBR)
● Click "Safe stop functions (SS1, SBR)" in the "Safety Integrated" dialog box to
parameterize SS1 and SBR.
● Go to page "SS1"
– "Delay time STOP F -> STOP B"
– "Shutdown speed SS1"
– "SS1 monitoring"
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Enter a value for the delay time here for the transition from STOP F to STOP B
(p9555).
Enter a value for the shutdown speed SS1 (p9560).
You can select whether you want to use SS1 with or without drive-autonomous OFF3
ramp (p9507) here.
Commissioning
6.7 Commissioning: Basic procedure
275

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents