● Change to the "SS2/SOS" page.
– "Delay time SS2/STOP C -> SOS active"
– "Delay time SOS -> SOS active"
– "Delay time for STOP D -> SOS active"
– "Delay time for STOP E -> SOS active"
– "Standstill tolerance SOS"
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
You can set the transition time from SS2/STOP C to SOS (p9552) here.
You can set the delay time for the activation of SOS (p9551) here. Please note that
this is the same timer value that is effective between the selection and activation of
SLS.
You can set the transition time from STOP D to SOS (p9553) here.
You can set the transition time from STOP E to SOS (p9554) here.
You can set the tolerance for the SOS function (p9530) here.
Commissioning
6.7 Commissioning: Basic procedure
257