Appendix
A.3 Acceptance tests (recommendations)
N o .
r9774.5 = r9774.6 = 1 (SS1 selected and active - group); only relevant for grouping
•
3.
Canceling SS1
No Safety faults and alarms (r0945[0...7], r2122[0...7])
•
r9772.22 = 0 (SS1 deselection via terminals – DI CU / EP terminal Motor Module); only
•
relevant for SS1 via terminal
r9772.23 = 0 (SS1 deselection via PROFIsafe); only relevant for SS1 via PROFIsafe
•
r9773.0 = r9773.1 = 0 (STO deselected and inactive – drive)
•
r9773.5 = r9773.6 = 0 (SS1 deselected and inactive – drive)
•
r9774.0 = r9774.1 = 0 (STO deselected and inactive – group); only relevant for grouping
•
r9774.5 = r9774.6 = 0 (SS1 deselected and inactive – group); only relevant for grouping
•
4.
Acknowledge switch-on inhibit and run the drive. Check whether the correct drive is operational.
424
D e scri p ti o n
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
Sta tu s
Safety Integrated