For the 7360 ISAM FX-16 and 7360 ISAM WM vertical mount configurations,
mounting kits are included with the shipment, and contain specific shelf mounting
brackets that must be used. Drip trays are required below each installed
7360 ISAM FX shelf, including below the bottom shelf of a rack when mounted on
combustible surfaces for safety purposes. A heat and fiber management baffle kit is
required directly above each 7360 ISAM FX shelf in the rack for safety and optical
fiber management purposes. And a fiber management kit is required for each shelf
to support optical fiber management and proper bend radius.
The 7360 ISAM FX-16 pre-installed rack contains:
For the 7360 ISAM FX-4 and 7360 ISAM FX-8 horizontal mount, specific shelf
horizontal mounting kits are required, depending on the size of the rack.
For the 7360 ISAM FX-4 and the 7360 ISAM FX-8 vertical mount, specific vertical
shelf mount kits are required, depending on the size of the rack. These kits must be
used for installation in compliance with safety specifications. The following hardware
is included in the kits:
Fiber management kits are recommended for each shelf to support optical fiber
management and proper bend radius.
See 7360 ISAM FX Product Information Guide for more information about mounting
kits.
Power must be supplied to the A and B power source at startup (boot time) or the
system will not initialize. This failure is because a FANALM alarm for fan 1 will be
raised if the fan unit is missing A- or B-side power. An alarm for this reason puts the
system in thermal shutdown mode. This mode ensures proper powering of the
equipment to protect the system from a potential thermal event.
Issue: 09
one or two factory installed 7360 ISAM FX-16 shelves
heat and fiber management baffle kit(s)
drip tray(s)
Pre-assembled horizontal mounting brackets and air intake baffles/drip trays are
required below each vertically installed shelf, including below the bottom shelf of
a rack when mounted on combustible surfaces to enhance the required airflow for
safety purposes.
Pre-assembled top cross brackets, rear skirts and front skirts are required to
contain possible flame spread damage to the equipment.
Intumescent panels are required for protection and increased air flow.
Top baffles are required for correct air flow, heat, and fiber management
purposes.
The vertical shelf mount kits must be used for the
Caution —
7360 ISAM FX-4 and 7360 ISAM FX-8 in a vertical mount
installation as the air intake baffle/drip tray and top baffle are
required to meet NEBS preferred airflow specifications (air
flows in the front, and out the rear of the shelf).