This section provides information about the types of power connection cables, cable
routing, and a procedure for connecting the power cables on the 7360 ISAM FX-16.
6.5.3.1
The 7360 ISAM FX-16 requires the use of a 2 AWG power cable.
6.5.3.2
The power cables are routed through the left side of the rack and can then be routed
to the power distribution terminal block located on the bottom of the shelf; see
Figure 39.
Issue: 09
Safety cover label
CAUTION: BEFORE REMOVING TERMINAL COVER,
DISCONNECT BOTH "A" AND "B" POWER SOURCES
CAUTION: TORQUE NUTS TO 65-LBS MAX
Power cables
Power cable type
The color of the power cables must be according to
Note 1 —
local installation practices.
Nokia recommends the following crimp lugs and
Note 2 —
tooling for −48 Vdc input and return:
•
input power lug: 2 AWG, 90C, Burndy YAZ2C-2TC14 or
equivalent
•
2 AWG 1/4 - 5/8 dual-hole copper lug, long barrel, peep,
uses Burndy Die Code 10. See Burndy catalog for additional
tool options.
•
input power lug: 2 AWG, 90C, Thomas and Betts
54855BEPH or equivalent
•
2 AWG 1/4 - 5/8 dual-hole copper lug, long barrel, peep,
uses Thomas and Betts Die Code 33. See Thomas and
Betts catalog for additional tool options.
All required washers and nuts are included with the
Note 3 —
shelf.
Power cable routing and connection
3HH-12893-AAAA-TCZZA
DRAFT
7360 ISAM FX-16 shelf cabling