Continued from the previous page
Options
Settings
• I Arm Analysis: opens the Edit Parameters page, to enable/disable
the calculation of harmonics for the currents.
• V Arm Analysis: opens the Edit Parameters page, to enable/disable
calculation of the harmonics for the voltages.
• Monitor Time, V Threshold Low, V Threshold High, Unbalance Th, V
microswitch Th, V Spike Threshold: they open the Edit Parameters
Network
page, to set the parameters (for details on the parameters, see the
Analyzer
chapter "16 - Hi-Touch measurements", and the paragraph "Network
Analyzer", on page 138).
• Sags: opens a list of the parameters that can be set for monitoring
voltage drops.
• Swells: opens a list of the parameters that can be set for monitoring
voltages swells.
• Enable: available if the function is not running, it opens the Edit
Parameters page, to enable/disable the function.
• Num. of Datalogger: available with Datalogger enabled, it opens the
Edit Parameters page, in order to set the number of records.
• Freq. Sampling: available with Datalogger enabled, it opens the Edit
Parameters page, to set the frequency of data logging.
• Datalogger 1: available with Datalogger enabled, opens a list of the
Datalogger
parameters that can be set and the commands of the function.
(2)
• Datalogger 2: available with the second Datalogger enabled, opens
a list of the parameters that can be set and the commands of the
function.
• Restart both: available with the second Datalogger enabled, it starts
both recordings.
• Stop both: available with the second Datalogger enabled, it stops
both recordings.
• Enable: opens the Edit Parameters page, to enable/disable dual
configuration of the protections.
Dual Set
(3)
• Default Set: available with Dual Set enabled, it opens the Edit
Parameters page, to set the default configuration.
• Date: opens the Edit Parameters page, to set the date.
• Time: opens the Edit Parameters page, to set the time
System
• Language: opens the Edit Parameters page, to set the language.
• New Password: it opens the page for insertion of the password.
• Switch On SET B: opens a list of the parameters for programming
the switching of protections from configuration A to configuration
Function
B, or vice versa (see the chapter "19 - Operating features", and the
paragraph "Functional specifications", on page 148).
• Signals: opens the Edit Parameters page, in order to enable/disable
the maintenance required signal, after a year from the last maintenance,
Maintenance
or with contact wear of at least 20% and an increase of 10% compared
to the last maintenance.
(1)
The options contained in the Modules submenu change according to the electronic accessories con-
nected.
(2)
Function available with the release energized with auxiliary voltage.
(3)
Setting available with Hi-Touch and G Hi-Touch releases.
ABB | SACE Emax 2
Ekip Touch protection release | 6 - Menu