Table of Contents

Advertisement

YR: remote resetting coil

R1
R2
YR
228 | © 2013 ABB | 1SDH001000R0002 - L7804
The remote resetting coil deactivates the lock at the closing of the circuit-breaker, generated by
the opening of the circuit-breaker caused by tripping of the Ekip protection release.
The tables listing the available voltages and the electrical characteristics are provided
below:
Available voltages (Un)
24V AC/DC
110V AC/DC
220V AC/DC
YR: Connections
Further information is available on page 156, or on the site http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
Diagram 14
Information on the assembly is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet 1SDH001000R0606.
General characteristics
Operating limits (Standards
IEC60947-2)
14
+
~
A4
SR
X
R1
XV
R1
A1
YR
XV
R2
X
R2
-
A4
~
Electrical accessories | 1 - Electrical Control accessories
ABB | SACE Emax 2
90%...110% Un

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sace emax e2.2Sace emax e4.2Sace emax e6.2

Table of Contents