Access from the display With the module energized, and the Local Bus enabled, the presence of the module on the
174 | © 2013 ABB | 1SDH001000R0002 - L7804
terminal box activates additional menus on the display :
• To configure the synchronism function.
• To display the measurements related to the function (voltage, frequency, and phase).
• To configure the module.
• To display information on the module and synchronism status.
To enable the Local Bus, you need to select "On" in the menu Settings, Modules, Local Bus.
The configuration parameters of the synchronism function are different depending on whether
the dead Bar option is enabled or not.
The following table illustrates the path from the display for accessing configuration parameters
of the function, and the parameters available with dead Bar disabled:
...
Protection UP
Advanced
Syncrocheck Protection
Signallings
...
The following table illustrates the path from the display for accessing configuration parameters
of the function, and the parameters available with dead Bar enabled:
...
Protection UP
Advanced
Syncrocheck Protection
Signallings
...
NOTE: the module can also be configured the Ekip Connect application (see the
chapter "13 - Other accessories", and the paragraph "Ekip Connect application" on
page 221).
Enable
Delta U Threshold
U Live Threshold
Delta Frequency
Delta Phase
Dead Bus Option (Off)
Enable
U Dead Threshold
U Live Threshold
Dead Bus Option (On)
Dead Bus Config
Continued on the next page
Electronic accessories | 3 - Ekip Synchrocheck module
ABB | SACE Emax 2