Signallings The following table provides a description of the signals of the interface:
Structure of the pages The following table illustrates how the pages shown on the display are structured:
57 | © 2013 ABB | 1SDH001000R0002 - L7804
LED
Description
The possible states are:
Green
• Off: power supply absent.
• On, fixed or flashing: power supply present, and release on.
The possible states are:
• Off: no warning or error.
• On, flashing quickly: absence of communication with the Mainboard, or
installation error (of the Rating Plug, Ekip Measuring or Ekip Measuring Pro
Yellow
module).
• On, flashing slowly: internal error.
• On, with two quick flashes every 0,5 s: parametrization error.
• On, fixed: prealarm of protection L, or circuit-breaker status error.
The possible states are:
• Off: no alarm or error.
• On, flashing quickly: absence of communication with the Mainboard, or trip
Red
coil disconnected, or current sensor disconnected, or delay active.
• On, with two quick flashes every 2 s: Rating Plug error.
• On, flashing slowly: internal error.
• On, fixed: signal that opening has occurred.
Level 1
Diagnosis bar.
Main page
NOTE: the level 3 pages are not graphical pages, and are dealt with in chapter "6 -
Menu" on page 65.
Level 2
Alarm list page
Histograms page
Menu page
Measuring instruments
pages
Measurements pages
Ekip Touch protection release | 1 - Layout of the interface
ABB | SACE Emax 2
Level 3
Basic protections menu
Advanced protections
menu
Measurements menu
Settings menu
Test menu
Information menu