The following table illustrates the configuration parameters of the synchronism function:
Parameter
Values
Enable
Off, On
0.02...0,12 Un
Delta U Threshold
in steps of 0.001 Un
0.05...0.20 Un
U Dead Threshold
in steps of 0.001 Un
0.5...1.1 Un
U Live Threshold
in steps of 0.001 Un
stability voltage time
1000...30000 ms
for live state
in steps of 1 ms
(3)
0.1...1.0 Hz
Delta Frequency
in steps of 0.1 Hz
5...50 °
Delta Phase
in steps of 5 °
minimum matching
100...3000 ms
Time
in steps of 10 ms
(3)
Dead Bus Option
Off, On
Frequency Check
ON, OFF
(3) (4)
Phase Check
ON, OFF
(3) (4)
evaluate CB status
NO, YES
(3)
Dead Bus Config
Reversed, Standard
(1)
With Bar dead, and "Reversed" configuration, the roles of the internal and external voltages are inverted.
(2)
On the condition of minimum voltage, a hysteresis of 10% is applied: once reached, the condition is lost if the voltage drops below 90% of the set
limit.
(3)
Parameter available only with the Ekip Connect application.
(4)
If the Frequency Check is disabled ("OFF"), the Phase Check is also Off, but not vice versa.
175 | © 2013 ABB | 1SDH001000R0002 - L7804
Default
Description
• Off = Function disabled.
Off
• On = Function enabled
With Bar live, 1
0.12 Un
between internal and external voltage.
With Bar dead, and "Standard" configuration, 1
0.2 Un
condition: maximum external voltage
Minimum voltage in order to start up monitoring of the voltages
• With Bar live, external under-voltage.
0.5 Un
• With Bar dead, and "Standard" configuration, internal under-
voltage
.
(1)
Time minimum in which the condition must be satisfied "U Live
1000 ms
Threshold", to start up monitoring of the voltages.
With Bar live, 2
0.1 Hz
between internal and external frequency.
With Bar live, 3
50 °
between internal and external phase.
With the Bar live, the minimum time within which the "Delta Phase"
condition must be satisfied: this is not a synchronism condition,
100 ms
but a parameter that allows you to discriminate between correct
combinations, rather than the "Delta Frequency" and "Delta Phase"
conditions.
• Off = Bar live.
Off
• On = Bar dead.
With Bar live, "Delta Frequency" condition:
ON
• OFF = Disabled.
• ON = Enabled.
With Bar live, "Delta Phase" condition:
ON
• OFF = Disabled.
• ON = Enabled.
Circuit-breaker open condition (With Bar live 4
condition, With Bar dead 2
NO
• NO = Disabled.
• YES = Enabled.
With Bar dead, and generator:
• Reversed = Ekip Synchrocheck/external contacts connected to
Standard
the generator
(1)
• Standard = Ekip Synchrocheck/external contacts connected to
the network.
synchronism condition: maximum difference
a
.
(1)
synchronism condition: maximum difference
a
synchronism condition: maximum difference
a
synchronism condition):
a
.
Electronic accessories | 3 - Ekip Synchrocheck module