Signallings

170 | © 2013 ABB | 1SDH001000R0002 - L7804
Continued from the previous page
The following table illustrates configuration parameters of the modules:
Parameter Values
Voltage
Absent, Present
Transformer
100 V, 115 V, 120 V, 190 V,
208 V, 220 V, 230 V, 240 V,
Rated
277 V, 347 V, 380 V, 400 V,
voltage
415 V, 440 V, 480 V, 500 V,
550 V, 600 V, 660 V, 690 V
100 V, 115 V, 120 V, 190 V,
208 V, 220 V, 230 V, 240 V,
Primary
277 V, 347 V, 380 V, 400 V,
voltage
415 V, 440 V, 480 V, 500 V,
550 V, 600 V, 660 V, 690 V,
910 V, 950 V, 1000 V, 1150 V
Secondary
100 V, 110 V, 115 V, 120 V,
voltage
200 V, 230 V
Flow of
Low->High, High->Low
power
The following table illustrates the path from the display for displaying information on the
modules:
Protection unit
Circuit-breaker
Information
Modules
Power Controller
The items of information on the modules that can be displayed are the serial number and the
version ("Basic" in the case of Ekip Measuring, "Pro" in the case of Ekip Measuring Pro).
The following table illustrates the possible signals, and their meaning:
A
Pos.
Description
Power status LED, green; present only on the Ekip Measuring Pro. The
possible states are:
A
• Off: the power supplied by the Ekip Measuring Pro to the release is absent.
• On fixed: the power supplied by the Ekip Measuring Pro to the release is
present.
Default
Description
• Absent = Isolation
transformer on the supply side
of the inputs of the module is
absent.
Absent
• Present = Isolation
transformer on the supply side
of the inputs of the module is
present.
Displayed with Voltage
Transformer set as absent,
100 V
the rated voltage of the
installation.
Displayed with Voltage
Transformer set as present,
100 V
the primary voltage of the
isolation transformer.
Displayed with Voltage
Transformer set as present,
100 V
the secondary voltage of the
isolation transformer.
• Low->High = Flow of power
from low terminals to high
terminals of the circuit-breaker
(load connected high).
Low->High
• High->Low = Flow of power
from high terminals to the low
terminals the circuit-breaker
(load connected low).
...