Access from the display With the modules powered, and Local Bus enabled, the presence of the modules on the
196 | © 2013 ABB | 1SDH001000R0002 - L7804
terminal box activates additional menus on the display, to configure the modules according to
the characteristics of the network.
To enable the Local Bus, you need to select "On" in the menu Settings, Modules, Local Bus.
The following table illustrates the path for accessing the configuration parameters of the
modules from the display:
...
Network frequency
Settings
Modules
Power Controller
...
(1)
Like the Ekip Com Modbus RS-485 menu.
The following table illustrates configuration parameters of the modules:
Parameter Values
Address
1... 247
9600 bit/s,
Baudrate
19200 bit/s
8.E,1, 8.O,1,
Protocol
8.N,2, 8.N,1
NOTE: the modules can also be configured with the Ekip Connect application (see
the chapter "13 - Other accessories", and the paragraph "Ekip Connect application"
on page 221).
The following table illustrates the path from the display for accessing information on the
modules:
Protection unit
Circuit-breaker
Information
Modules
Power Controller
Local/Remote
Local Bus
...
Ekip Com Modbus RS-485
Ekip Com Modbus RS-485 bus *R
...
Function
Default
Description
• Ekip Com Modbus
Address to be assigned to the modules.
RS-485: 247
• Ekip Com Modbus
RS-485 Redundant:
246
19200 bit/s
Data transmission speed
• 8.E,1 = 8 data bits, 1 EVEN parity bit,
1 STOP bit.
• 8.O,1 = 8 data bits, 1 ODD parity bit,
1 STOP bit.
8,E,1
• 8.N,2 = 8 data bits, no parity bit, 2
STOP bits.
• 8.N,1 = 8 data bits, no parity bit, 1
STOP bit.
...
Ekip Com Modbus RS-485
Ekip Com Modbus RS-485 bus *R
...
Electronic accessories | 6 - Ekip Com Modbus RS-485 modules
ABB | SACE Emax 2
Address
Baudrate
Protocol
(1)
IMPORTANT: devices connected
to the same network must have
different addresses.