Summary table for G Touch protections

ABB
ANSI
Threshold
(5)
I20 = 0.6...10 In; Step = 0.1 In
S(V)
51V
Ul = 0.2...1 Un; Step = 0.01 Un
(Step)
Ks = 0.1...1; Step = 0.01
I20 = 0.6...10 In; Step = 0.1 In
S(V)
Ul = 0.2...1 Un; Step = 0.01 Un
51V
(Linear)
Uh = 0.2...1 Un; Step = 0.01 Un
Ks = 0.1...1; Step = 0.01
U22 = 0.1....0.5 Un
RV
59N
Step = 0.001 Un
Q24 = -1...-0.1 Sn; Step = 0.001
RQ
40/32R
Sn
Kq = -2...2; Step = 0.01
P26 = 0.4...2 Sn
OP
32OF
Step = 0.001 Sn
Q27 = 0.4...2 Sn
OQ
32OF
Step = 0.001 Sn
P23 = 0.1...1 Sn
UP
32LF
Step = 0.001 Sn
Table of Additional Functions of the protections
Protection UP has Startup Enable:
ABB
UP(Startup)
Notes
(1)
The calculation of t
is valid for values that have exceeded the activation threshold of the protection.
t
(2)
Valid tolerances with release energized in service conditions or with the auxiliary, tripping time = 100 ms, temperature and currents within operating
limits. If the conditions are not guaranteed, the tolerance of the tripping time becomes ± 20%.
(3)
The tripping threshold of the current for voltage values between Ul and Uh is calculated by performing the linear interpolation between the th-
resholds Uh and I20 (first point on the line) and Ul and Ks * I20 (second point on the line). I
(4)
The startup of protection UP is to be considered as the temporary deactivation time of the protection, starting from the exceeding of the startup
threshold.
(5)
ANSI / IEEE C37-2 encoding.
116 | © 2013 ABB | 1SDH001000R0002 - L7804
Tolerance
threshold
± 10 %
± 10 %
± 5 %
± 10 %
± 10 %
± 10 %
± 10 %
Time
(4)
t23
= 0.1...30 s
startup
step = 0.01 s
Calculation
Tripping time
formula t
t20 = 0.05...30 s
t
= t20
Step = 0.01 s
t
t20 = 0.05...30 s
t
= t20
Step = 0.01 s
t
t22 = 0.5...60 s
t
= t22
Step = 0.05 s
t
t24 = 0.5...100 s
t
= t24
Step = 0.1 s
t
t26 = 0.5...100 s
t
= t26
Step = 0.5 s
t
t27 = 0.5...100 s
t
= t27
Step = 0.5 s
t
t23 = 0.5...100 s
t
= t23
Step = 0.5 s
t
= [(I20 * Ks *I20) / (Uh * Ul)] / (U
threshold
Ekip Touch protection release | 12 - G Touch protections
ABB | SACE Emax 2
Tolerance t
(3)
(2)
t
t
The better of the
two values:
± 10% or ± 40 ms
The better of the
two values:
(4)
± 10% or ± 40 ms
The better of the
two values:
± 10% or ± 40 ms
The better of the
two values:
± 10% or ± 40 ms
The better of the
two values:
± 10% or ± 40 ms
The better of the
two values:
± 10% or ± 40 ms
The better of the
two values:
± 10% or ± 40 ms
* Uh) + I20.