181 | © 2013 ABB | 1SDH001000R0002 - L7804
Continued from the previous page
The following table illustrates configuration parameters of the outputs:
Parameter Selectable values Default
• None
• Prealarm L
• Delay L
• Delay S
• Opening L
• Opening S
• Opening G
Signal
• Opening I
source
• Every opening
• Every alarm
• Load LC1
(1)
• Load LC2
(1)
• CB Open
• CB Close
• Custom
(2)
00...100.00 s
Delay
in steps of 0.01 s
Contact
NO, NC
Type
Self-
Off, On
latching
min
0 ms, 100 ms,
Activation
200 ms, Power
Time
Controller
(1)
For the sources Load LC1 and Load LC2, see the chapter "9 - Touch protections", and the paragraph "
Current thresholds", on page 91.
(2)
The Custom source is a combination of default events, that can be modified using the Ekip Connect
application so as to make the closing/opening of the contact correspond to a wide range of combinations
of the status bits of the release.
Description
The event that the output must activate, that is,
with which the contact must be:
None
• Closed, if set as NO.
• Open, if set as NC.
Standby time after the selected event has taken
place, and before the output is activated (if the
event disappears before a time equal to the delay
0.00 s
has passed, the output is not activated). If 0.00 s
is selected, the value 300 μs is assigned to the
parameter.
• NO = Contact normally open.
NO
• NC = Contact normally closed.
• Off = The output is deactivated when the event
disappears.
• On = When the event disappears, the output is
kept active for the minimum time selected.
Off
IMPORTANT: if the output is used for the
Power Controller function, self-latching
must not be enabled.
The "Power Controller" value must be selected
if the output is used for the Power Controller
function (see the chapter "21 - Ekip Power
Controller", on page 151). The output is then
kept active for a fixed time dictated by the
function, independently of the persistence of the
event that activated it.
On the contrary, with self-latching enabled, the
0 ms
minimum time in which the output is kept active
(once the selected time has elapsed, the output
is kept active as long as the event that activated
it persists).
IMPORTANT: if the output is not used
for the Power Controller function, the
"Power Controller" value must not be
selected.
Electronic accessories | 4 - Ekip Signalling 4K module
ABB | SACE Emax 2
Continued on the next page