188 | © 2013 ABB | 1SDH001000R0002 - L7804
Continued from the previous page
The following table illustrates configuration parameters of the outputs:
Parameter
Selectable values
• None
• Prealarm L
• Delay L
• Delay S
• Opening L
• Opening S
• Opening G
Signal
• Opening I
source
• Every opening
• Every alarm
• Load LC1
• Load LC2
• CB Open
• CB Close
• Custom
(2)
00...100.00 s
Delay
in steps of 0.01 s
Contact
NO, NC
Type
Self-latching Off, On
min
0 ms, 100 ms,
Activation
200 ms, Power
Time
Controller
(1)
For the sources Load LC1 and Load LC2, see the chapter "9 - Touch protections", and the paragraph "
Current thresholds", on page 91.
(2)
The Custom source is a combination of default events, that can be modified using the Ekip Connect
application so as to make the closing/opening of the contact correspond to a wide range of combinations
of the status bits of the release.
Default
Description
The event that the output must activate,
that is, with which the contact must be:
None
• Closed, if set as NO.
• Open, if set as NC.
(1)
(1)
Standby time after the selected event
has taken place, and before the output is
activated (if the event disappears before
0.00 s
a time equal to the delay has passed,
the output is not activated). If 0.00 s is
selected, the value 300 μs is assigned to
the parameter.
• NO = Contact normally open.
NO
• NC = Contact normally closed.
• Off = The output is deactivated when
the event disappears.
• On = When the event disappears, the
output is kept active for the minimum time
Off
selected.
IMPORTANT: if the output is used
for the Power Controller function,
self-latching must not be enabled.
The "Power Controller" value must be
selected if the output is used for the Power
Controller function (see the chapter "21 -
Ekip Power Controller", on page 151). The
output is then kept active for a fixed time
dictated by the function, independently of
the persistence of the event that activated
it.
On the contrary, with self-latching enabled,
0 ms
the minimum time in which the output is
kept active (once the selected time has
elapsed, the output is kept active as long
as the event that activated it persists).
IMPORTANT: if the output is not
used for the Power Controller
function, the "Power Controller"
value must not be selected.
Electronic accessories | 5 - Ekip Signalling 2K modules
ABB | SACE Emax 2
Continued on the next page