  • Page 3: Table Of Contents

    1 - Measurement ................29 Ekip Touch - Default ................30 1 - Ekip TOUCH default parameters ......... 30 Management operations ..............31 1 - Ekip Touch maintenance and troubleshooting ....31 1 | © 2023 ABB | SACE Emax 2 1SDH001316R1002 - ECN000297030...
  • Page 4 2 | © 2023 ABB | SACE Emax 2 1SDH001316R1002 - ECN000297030...
  • Page 5: Glossary

    CB if faulty operating conditions occur. In the event of an alarm, it commands a TRIP Ekip Touch Trip unit for SACE Emax 2 CBs, equipped with touchscreen display and available in four different versions Trip coil CB opening actuator controlled directly by Trip unit...
  • Page 6: Introduction

    ABB | SACE Emax 2 Introduction 1 - Contents Overview This manual describes the characteristics of the Ekip Touch Trip units installed on SACE Emax 2 CBs, among which: general overview: operating conditions consultation of menus for changing parameters and displaying measurements...
  • Page 7: Safety

    • anyone who is implementing procedures or using maintenance devices recommended by ABB or not must check carefully that neither their personal safety nor the safety devices are endangered by the installation, operation, maintenance method or by the tools used; contact your nearest ABB representative for further information, explanations or specific problems •...
  • Page 8: Trip Unit Overview

    Trip unit Overview 1 - General characteristics Main functions SACE Emax 2 can be configured using the Ekip Touch trip unit, which is available in several versions and able to provide, protection, measurement and signalling functionalities. Emax 2 can be provided with mechanical, electronic and testing accessories, and is supported by many different types of software and applications enabling the functions of the Trip unit and circuit-breaker to be expanded.
  • Page 9 Auxiliary power supply can be provided by modules from the || Ekip Supply|ii| range or by direct connection to the terminal box; a direct connection can also be made. Details are available in the manual 1SDH001330R1002. 7 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Trip unit Overview 1 - General characteristics...
  • Page 10: Ekip Touch - Interface And Menus

    Figure 2 Pos. Description Single-touch color touchscreen display LED Power LED Warning LED Alarm HOME push-button iTEST push-button Service connector 8 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Ekip Touch - Interface and menus 1 - Presentation of interface...
  • Page 11 IMPORTANT: only use cables supplied by ABB or with ABB accessories 9 | © 2023 ABB | 1SDH001316R1002 - ECN000297030...
  • Page 12: Navigation

    Each submenu has a command for returning to the previous menu (11); if the list contains more than five options, there is also a scroll bar (12) for full consultation. evel evel evel evel Figure 3 10 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Ekip Touch - Interface and menus 2 - Navigation...
  • Page 13: Changing Parameters And Commands

    • Abort to interrupt the save data process • Modify to go back to the menus and change the parameter or others Figure 7 11 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Ekip Touch - Interface and menus 3 - Changing parameters and commands...
  • Page 14 • if the Trip unit detects an incorrect condition, the relative details appear on the display and command execution is annulled. WARNING! aborting the programming affects all the parameters modified during the same session 12 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Ekip Touch - Interface and menus 3 - Changing parameters and commands...
  • Page 15: Pin And Security

    To ensure your unit is in secure conditions, the Wizard window immediate asks you to change the PIN code on first power up; this is strongly recommended by ABB. Description The PIN code is a number formed by five digits, each of which can be given a value from 0 to 9; the default value is: 00001 and can be changed in the Settings - New PIN menu.
  • Page 16: Protections

    Type of protection Reference Description Current Nominal current of the Rating plug Voltage Line-to-line voltage setting Frequency Frequency setting Power √3 x In x Un 14 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Protections 1 - Protections - Introduction...
  • Page 17: Standard Protections

    Direction of current flow Further details about the protections are given in document 1SDH001330R1002. protection cannot be deactivated; its trip parameters are set by ABB and cannot be edited not available with LSI version of Trip unit can be activated with protection MCR = Disable can be activated with protection I = Disable if the presence of sensor S.G.R.
  • Page 18 All protections enabled in the unit are active in all operating states. Other protections The Iinst, Harmonic distortion, Hardware trip and Current threshold protections are described in detail in the manual 1SDH001330R1002. Continued on the next page 16 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Protections 2 - Standard Protections...
  • Page 19 (for a time step = 1 % step = 0.5 s set < 5 s) / ± 100 ms (for a time set ≥ 5 s) Continued on the next page 17 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Protections...
  • Page 20 ± 20 % ± 15 % ≤ 60 ms ± 15 % ± 20 % (60 ms with t4 = instantaneous) ± 15 % ≤ 60 ms Other ± 20 % 18 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Protections...
  • Page 21: Voltage Protections

    ANSI / IEEE C37-2 codification protection not active if the higher of the voltages measured is less than 0.3 Un the trip unit considers 3% hysteresis for quitting alarm condition 19 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Protections...
  • Page 22: Voltage Advanced Protections

    (11) tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current values within operating limits; the tolerance value is ± 10% if the conditions are not guaranteed 20 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Protections...
  • Page 23: Frequency Protections

    32 V with hysteresis at 36 V tolerance valid for frequencies within range: fn ± 2%; a ± 5% tolerance is available for off range frequencies 21 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Protections...
  • Page 24: Power Protections

    (TRIP OFF is signaled); the protection is also active for negative active power, but is independent of RP protection (Protection from inverse active power) Continued on the next page 22 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Protections...
  • Page 25: Rocof Protections

    The function can be activated and the Set of the main protections configured in the Settings - Double Set menu; the event that determines Set change (from main to secondary) can be programmed in the Advanced - Functions menu. 23 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Protections...
  • Page 26: Additional Protections And Functions

    Changes the configuration, from Remote to LOCAL Switch On Settings - Modules Local - Functions Signaling RESET Reset the contacts of the signalling modules 24 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Protections 9 - Additional protections and functions...
  • Page 27: Ekip Touch - Measurements

    Deactivated ) and the serial numbers of certain accessories installed on the CB for the specific purpose of conforming to the characteristics of the package (electronic units and internal current sensors) 25 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Ekip Touch - Measurements...
  • Page 28: Ekip Touch - Settings

    Ekip Touch is supplied with the parameter setting that suits the ordered configuration. 26 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Ekip Touch - Settings 1 - Main settings...
  • Page 29 Access to the LOCAL Switch On and RESET signaling functions Functions Bluetooth Low Energy - Details of connection Security are available in manual 1SDH0013300R1002. Connection security 27 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Ekip Touch - Settings 1 - Main settings...
  • Page 30 (trips or measurements); in the event of date and time glitches, reset and if necessary replace the battery inside Ekip Touch (page 31). 28 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Ekip Touch - Settings 1 - Main settings...
  • Page 31: Accessories

    • Confirm the installation module which appears automatically on the display WARNING! if the Class 1 Power & Energy Metering package is present, module replacement will impair the performance values indicated on page 25; consult ABB to assess solutions able to comply with your requirements 29 | ©...
  • Page 32: Ekip Touch - Default

    Modbus RTU par Address: 247; baudrate: 19.2 kbit/s Profibus Address: 125 DeviceNet MAC ID: 63; baudrate: 125 kbit/s Modbus TCP/IP Static IP: 0.0.0.0 30 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Ekip Touch - Default 1 - Ekip TOUCH default parameters...
  • Page 33: Management Operations

    Signal Suggestions Numerical alarm Internal error; contact ABB if this typoe of error occurs (e.g. 30002) Unit on with auxiliary supply, Local Bus parameter enabled but connection to modules not present, incorrect or communication lost (for more than five Local bus seconds);...
  • Page 34 Continued from the previous page Signal Suggestions Internal error Internal error; contact ABB if this typoe of error occurs Fault with Ekip Com modules: synchronization problem of SNTP SNTP error synchronization reference module Measurement module parameter reading error, contact ABB...
  • Page 35 NOTE: check error messages on display before consulting the table; if the suggestions given fail to resolve the problem, call the ABB assistance service and provide the report produced by the Ekip Connect software if possible...
  • Page 36 The operating mechanism is blocked Contact ABB the manual charging lever Continued on the next page 34 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Management operations 1 - Ekip Touch maintenance and troubleshooting...
  • Page 37 Press the opening pushbutton and to lock the circuit- pressed activate the lock breaker in the open The lock in open position is defective Contact ABB position Check Trip coil connection and Trip coil is not connected properly messages on display...
  • Page 38 4. Working in safety conditions, close the CB and perform a trip test via the trip unit Contact ABB if problems persist 36 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Management operations 1 - Ekip Touch maintenance and troubleshooting...
  • Page 39 ABB | SACE Emax 2 37 | © 2023 ABB | 1SDH001316R1002 - ECN000297030 Management operations 1 - Ekip Touch maintenance and troubleshooting...
  • Page 40 We reserve the right to make technical changes or modify the contents of this document without prior notice. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein.