Table A-17 Requirements for humidity, temperature, and cleanness in the equipment room
Item
Cleannes
s
Humidity
and
temperat
ure
To meet the requirements listed in
room:
l
l
l
l
l
l
Issue 08 (2017-06-30)
Description
Dust
Maximum
particl
diameter
e
(μm)
Maximum
density
(number of
dust
particles per
cubic meter)
Noxio
Gas
us gas
Average
density
(mg/m
Maximum
(mg/m
Tempe
Long-term
rature
operating
temperature
Short-term
operating
temperature
Operating humidity
Storage humidity
Install a permanent temperature controller regardless of the climate conditions.
In dry regions, use humidifiers or regularly mop the floor to ensure proper humidity in
the equipment room.
In regions with high humidity, use dehumidifiers.
Use dust-free materials for the floor, walls, and ceilings.
Screen exterior doors and windows. The external windows of the equipment room
should be sealed for anti-dust purposes.
Clean the equipment room and air filters on the devices once every three months.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
0.05
7
1.4 x 10
SO
H
S
2
2
0.3
0.1
3
)
1.0
0.5
3
)
l Without hard disk: 0 °C to 45 °C
l With hard disk(s): 5 °C to 40 °C
l Without hard disk: -5 °C to 55 °C
l With hard disk(s): 5 °C to 40 °C
l Without hard disk: 5% RH to 95% RH, non-
condensing
l With hard disk(s): 5% RH to 90% RH, non-
condensing
l Without hard disk: 5% RH to 95% RH, non-
condensing
l With hard disk(s): 5% RH to 90% RH, non-
condensing
Table
A-17, take the following measures in the equipment
1
3
5
5
7 x 10
2.4 x 10
CI
HCl
HF
NH
2
0.1
0.1
0.0
1.0
1
0.3
0.5
0.0
3.0
3
A Appendix
5
5
1.3 x 10
O
NO
3
3
2
0.
0.5
05
0.
1.0
1
393

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents