8.3 Reactive Power Adjustment
Before setting Reactive power control mode, set Reactive power control to Enable.
8.3.1 Disabling Reactive Power Output
If the PV plant is not required to adjust the voltage at the grid-tied point or perform reactive
power compensation, the inverter can run with pure active power output. In this case, set
Reactive power control mode to Disable reactive power output.
Figure 8-9 Reactive power control
8.3.2 Dry Contact Remote Control
Set Reactive power control mode to Dry contact remote control.
Issue 04 (2018-04-10)
If ports of DI5–DI8 have been configured in
Setting DI
Parameters, Dry contact remote control is unavailable.
Before setting dry contact remote control, ensure that the SmartLogger connects to a correct ripple
control receiver. For details, see
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7.10.6 Remote Shutdown over Dry Contacts
4.10 Connecting a Ripple Control
8 Power Grid Scheduling