No.
Parameter
32
Level-6 OV
protection
33
Level-6 OV
protection
time
Level-5 UV
34
protection
35
Level-5 UV
protection
time
Level-6 UV
36
protection
37
Level-6 UV
protection
time
38
Level-3 OF
protection
39
Level-3 OF
protection
time
40
Level-4 OF
protection
41
Level-4 OF
protection
time
42
Level-5 OF
protection
Level-5 OF
43
protection
time
44
Level-6 OF
protection
Level-6 OF
45
protection
time
Issue 04 (2018-04-10)
Description
Specifies the level-6
overvoltage protection
threshold.
Specifies the level-6
overvoltage protection
duration.
Specifies the level-5
undervoltage protection
threshold.
Specifies the level-5
undervoltage protection
duration.
Specifies the level-6
undervoltage protection
threshold.
Specifies the level-6
undervoltage protection
threshold.
Specifies the level-3
overfrequency protection
threshold.
Specifies the level-3
overfrequency protection
duration.
Specifies the level-4
overfrequency protection
threshold.
Specifies the level-4
overfrequency protection
duration.
Specifies the level-5
overfrequency protection
threshold.
Specifies the level-5
overfrequency protection
duration.
Specifies the level-6
overfrequency protection
threshold.
Specifies the level-6
overfrequency protection
duration.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Unit
Value Range
V
[1xVn, 1.5xVn]
ms
[50, 7200000]
V
[0.15xVn, 1xVn]
ms
[50, 7200000]
V
[0.15xVn, 1xVn]
ms
[50, 7200000]
Hz
[1xFn, 1.15xFn]
ms
[50, 7200000]
Hz
[1xFn, 1.15xFn]
ms
[50, 7200000]
Hz
[1xFn, 1.15xFn]
ms
[50, 7200000]
Hz
[1xFn, 1.15xFn]
ms
[50, 7200000]
7 WebUI
Remarks
Vn represents the
rated voltage.
Vn represents the
rated voltage.
Vn represents the
rated voltage.
Fn represents the
rated frequency.
Fn represents the
rated frequency.
Fn represents the
rated frequency.
Fn represents the
rated frequency.