Huawei SmartLogger2000 User Manual page 137

Hide thumbs Also See for SmartLogger2000:
Table of Contents

Advertisement

SmartLogger2000
User Manual
Running parameters
Figure 7-22 Running parameters
Issue 04 (2018-04-10)
Baud rate is set to 115200 by default, which provides optimal communications performance and
does not need to be changed.
If Anti-crosstalk is set to Enable, the inverter with a PLC STA in the SN list can access networking.
Parameters Box-type transformer No. and Winding No. can be set for the PLC CCO with
SUN2000 V100R001C72SPC100 or later versions. In multi-split transformer scenarios, specify
Winding No. based on the actual winding number of the SmartLogger connected to the transformer.
When the box-type transformer and winding numbers of the inverter with an STA are consistent with
those of the PLC CCO, the inverter can access networking.
When the PLC CCO is SUN2000 V100R001C72SPC104 or later versions, you can set Networking.
When the SmartLogger communicates with the inverter over PLC, set Networking to Enable
(default value).When the SmartLogger communicates with the inverter only over RS485, set
Networking to Disable.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 WebUI
127