ABB i-bus
KNX
Start-up
3.2.6.2

Parameter window A: Status messages

Settings for the status messages and their send reaction are undertaken in this parameter window.
Enable communication object
"Status Open-Closed/On-Off" 1 bit
Options:
Yes: The communication object Status Open-Closed/On-Off is enabled. The following parameter
appears:
Enable communication object
"Status Operability" 1 bit
Options:
This function is particularly suitable to indicate to the user via an LED that the output cannot currently be
operated via the direct communication ibjects (e.g. UP, DOWN...).
Yes: The communication object Status Operability is enabled. The following parameter appears:
Yes
No
Send object value
Options:
No, update only
On change
On request
On change or on request
No, only update: The status is updated but not sent (the status can be read via the
communication object).
On change: The status is sent when a change occurs.
On request: The status is sent when a request occurs.
On change or on request: The status is sent on a change or a request.
Yes
No
Operation is blocked if
a safety function was activated, e.g. Weather alarm, Disable or Forced operation
manual operation is active