ABB i-bus
KNX
Start-up
No.
28
Incoming telegrams at this communication object are only executed if automatic control is activated and if a 0 was received
at the Presence communications object and Overheat control was activated.
The room temperature, for example from a room thermostat, can be received via this communication object. The
blind/shutter moves to the parameterized position as soon as the parameterized threshold value has been exceeded and the
value 1 was received on the communication objects Heating and Sun. Thus, for example, during the heating period (winter),
overheating of the room can be avoided during periods of sunshine and simultaneous absence.
29
This communication object is enabled when automatic control is active and in the parameter window A: Automatic sun
protection, p. 75, the parameter Toggling to automatic control was selected with the option Disable/enable via object.
If a telegram with the value 1 is received at this communication object, automatic control is disabled and the output can only
be controlled directly via communication objects. Automatic control can no longer be activated via the communication object
Activation of autom. control.
If a telegram with the value 0 is received at this communication object, automatic control can be reactivated again for the
corresponding output.
Telegram value:
30
This communication object is enabled when automatic control is active and in the parameter window A: Automatic sun
protection, p. 75, the parameter Toggling to direct control was selected with the option Disable/enable via object.
If a telegram with the value 1 is received on this communication object, the incoming telegrams will not be executed directly
at the communication objects (with the exception of Travel detection/Trigger reference movement).
If a telegram with the value 0 is received at this communication object, direct operation is enabled. However, direct telegrams
(UP, DOWN, etc.) are only executed when automatic control is deactivated. Otherwise, automatic control has a higher
priority and direct telegrams are not taken into account.
Telegram value:
31
If a telegram with the value 1 is received, the output can be moved to a parameterized position. Operation of the output via
direct automatic communication objects is disabled. When the disabling is lifted, the blind/shutter is moved to the
parameterized position for the removal of Wind alarm, Block and Forced operation. Operation via the direct and automatic
communication objects is enabled again.
Telegram value:
32
If a telegram with the value 1 is received, the output can be moved to a parameterized position. Operation of the output via
direct automatic communication objects is disabled. When the disabling is lifted, the blind/shutter is moved to the
parameterized position for the removal of Wind alarm, Block and Forced operation. Operation via the direct and automatic
communication objects is enabled again.
Telegram value:
104 2CDC 506 051 D0204 | JRA/S
Function
Receive room temperature
Disable/enable autom. control
0 = Automatic control enabled
1 = Automatic control disabled
Disable/enable direct control
0 = Direct operation enabled
1 = Direct operation disabled
Block
0 = Operation enabled
1 = Operation disabled
Forced operation 1 bit
0 = Operation enabled
1 = Operation disabled/Forced operation active
Object name
Output A
Output A
Output A
Output A
Output A
Data type
Flags
2-byte
C, R, T, U
DPT 9.001
1 bit
C, R, T, U
DPT 1.001
1 bit
C, R, T, U
DPT 1.003
1 bit
C, R, T, U
DPT 1.003
1 bit
C, R, T, U
DPT 1.003