ABB i-bus
KNX
Device technology
2.5

Mounting and installation

The ABB i-bus
installation in distribution boards on 35 mm mounting rails to DIN EN 60 715.
The mounting position can be selected as required.
The connection to the bus is implemented using the supplied bus connection terminal.
The electrical connection is implemented using screw terminals. The connection to the bus is implemented
using the supplied bus connection terminal. The terminal assignment is located on the housing.
The device is ready for operation after connection to the bus voltage. If bus voltage is not yet available at
the time of commissioning, the devices can be supplied with power for operation of the manual
pushbuttons using the Power Supply NTI/Z.
Accessibility to the device for the purpose of operation, testing, visual inspection, maintenance and repair
must be provided compliant to VDE 0100-520.
Commissioning requirements
In order to commission the device, a PC with ETS and a KNX interface, e.g. USB or IP, are required. The
device is ready for operation after connection to the bus voltage.
Mounting and commissioning may only be carried out by electrical specialists. The appropriate standards,
guidelines, regulations and specifications for your country should be observed when planning and setting
up electrical installations and security systems for intrusion and fire detection.
Protect the device from moisture, dirt and damage during transport, storage and operation.
Only operate the device within the specified technical data!
The device should only be operated in an enclosed housing (distribution board)!
The voltage supply to the device must be switched off before mounting work is performed.
To avoid dangerous touch voltages which originate through feedback from differing phase conductors,
all poles must be disconnected when extending or modifying the electrical connections.
Manual operation
The device incorporates manual operating features. Special device functions can be undertaken using the
operating keys on the foil keypad.
The foil keypad may not be operated with pointed or sharp-edged objects, e.g. screwdrivers or pens. This
may damage the keypad.