ABB i-bus KNX Product Manual page 47

Blind/roller shutter actuators jra/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Start-up
Reset manual operat. to KNX operation
Options:
This parameter determines for how long manual operation remains activated or after how long switch over
to KNX operation occurs. It appears when the parameter option Disable/enable via object or Enable is
selected.
Via push button: Manual operation remains activated until it is deactivated again using the manual
operation button
Automatically and via push button: Manual operation remains activated after the last operation of the
button until the parameterized time has timed out or it is deactivated again using the manual button
. The following parameter appears:
Enable communication object
"Status Man. operation" 1 bit
Options:
Yes: The parameter Send object value and the communication object Status Man. operation appear.
Note
Safety telegrams, such as Weather alarms, Block and Forced operation have the highest priority and
block manual operation. If a safety telegram becomes active during manual operation, then the
parameterized safety position is moved to. Manual operation of the affected output is blocked as long as
the safety function is active.
Via push button
Automatically and via push button
or using the communication object.
Time for automatic reset
in s [10...6,000]
10...300...6,000
Options:
Manual operation remains activated until the parameterized time has timed out or it is deactivated
again using the manual button
No
Yes
Send object value
Options:
No, update only
On change
On request
On change or on request
No, only update: The status is updated but not sent (the status can be read via the
communication object).
On change: The status is sent when a change occurs.
On request: The status is sent when a request occurs.
On change or on request: The status is sent on a change or a request.
.
JRA/S | 2CDC 506 051 D0204 45