Code table for communication object Status information (Bit 0...7)

A.3
The 2-byte communication object Status information makes information on the operating state of the
output and connected drives available. The communication object Status information can be sent to the
KNX via the inter-device communication object Request status values.
For further information, see: Communication object no. 39 ff and No. 1.
The communication object Status information is divided up into two 1-byte values:
Bit 0...7 = Low Byte
Bit 8...15 = High Byte
The Low Byte shows the operating states of the output. Only one operating state can ever be active (1 n)
In the High Byte, additional status information on the output is made available. Multiple items of
information may be active simultaneously.
Low Byte code table; Operation mode Control with slat adjustment
Bit no. 7
0
00
1
01
2
02
4
04
8
08
16
10
32
20
64
40
128
80
Othe
Othe
r
Empty = Value 0
6
5
4
3
2
1
-
-
-
-
-
-
-
r
= Value 1, applicable
0
Current
status
Operation
Direct positioning
Via CO
- Up/down
- Stop/slat adj.
- Move to position
- Scene
Using the Up/Down
Manual operation
buttons
Block
Disabled
Forced operation
Disabled
Frost alarm
Disabled
Rain alarm
Disabled
Wind alarm
Disabled
Automatic sun
Via communication
protection
objects:
– Sun
– Sun position
– Sun slat
Automatic
Via communication
heating/cooling
objects:
– Heating
– Cooling
-
Not defined