Communication Objects Output A - ABB i-bus KNX Product Manual

Blind/roller shutter actuators jra/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Start-up
Communication objects Output A...X Operation mode Ventilation flaps, switch mode
3.3.4
No.
10
If a telegram with the value 1 is received at this communication object, then the output contact closes. The connected
ventilation flaps are thus opened and connected consumers are switched on. If a telegram with the value 0 is received, then
the ventilation flaps or the consumers are switched off. The output contact returns to the neutral middle position. The polarity
of the communication object can be changed via the parameter Invert output.
Telegram value:
31
If a telegram with the value 1 is received the output will move to a parameterized position. Operation of the output via direct
automatic communication objects is disabled. When the disabling is lifted, the blind/shutter moves to the parameterized
position for the removal of Wind alarm, Block and Forced operation. Operation via the direct and automatic communication
objects is enabled again.
Telegram value:
32
If a telegram with the value 1 is received the output will move to a parameterized position. Operation of the output via direct
automatic communication objects is disabled. When the disabling is lifted, the blind/shutter moves to the parameterized
position for the removal of Wind alarm, Block and Forced operation. Operation via the direct and automatic communication
objects is enabled again.
Telegram value:
32
If a telegram with the value 2 (binary 10) is received at this communication object, then the output contact closes. The
connected ventilation flaps are thus opened and connected consumers are switched on. Operation via direct communication
objects is disabled.
If a telegram with the value 3 (binary 11) is received, then the ventilation flaps or the consumers are switched off. Operation
via direct communication objects is disabled.
Forced operation is rescinded by the values 0 (binary 00) or 1 (binary 01). The output then activates the position on
rescinding of Wind alarm, Block and Forced operation. Operation via the direct communication objects is enabled again.
Telegram value:
33
The output sends information to this communication object on whether the ventilation flap is opened or closed or whether
connected consumers are switched on or switched off. The current status is sent after a telegram is executed. If a new
telegram is received in the interim, then the current status is only sent after the execution of the last telegram.
Telegram value:
Function
Flaps open-closed/on-off
0 = CLOSED/OFF
1 = OPEN/ON
Block
0 = Operation enabled
1 = Operation disabled
Forced operation 1 bit
0 = Operation enabled
1 = Operation disabled/Forced operation active
Forced operation 2 bit
0 (binary 00) = Operation enabled
1 (binary 01) = Operation enabled
2 (binary 10) = OPEN/ON - Operation disabled
3 (binary 11) = CLOSED/OFF - Operation disabled
Status Open-closed/on-off
0 = Ventilation flaps CLOSED or switching contact OFF
1 = Ventilation flaps OPEN or switching contact ON
Object name
Output
Output A
Output A
Output A
Output A
Data type
Flags
1 bit
C, W
DPT 1.009
1 bit
C, R, T, U
DPT 1.003
1 bit
C, R, T, U
DPT 1.003
2 bit
C, R, T, U
DPT 2.001
1 bit
C, R, T
DPT 1.011
JRA/S | 2CDC 506 051 D0204 107